Pre Moulded Cable Terminations 1 Core for 12kV (XLPE/EPR Insulated Cable)

Pre Moulded Cable Terminations 1 Core for 12kV (XLPE/EPR Insulated Cable)

  1. Cold-applied.
  2. No Special Tools.
  3. Constant Radial Pressure.
  4. In Built Stress Control Arrangement.
  5. Un limited Shelf Life.
  6. In compliance with HD629-1 & IEC-60502-4.
  7. Lugs are optional. Compression or shear head mechanical lugs supplied on request.
Specifications

Pre Moulded Straight Terminations are Tested as per HD629-1 & IEC-60502-4 / IS:13573

Testing Items Uo/U/Um6.35/11/12 kV
A.C. withstand test29kV, 5min, no flashover
Partial discharge test11kV<10pc (Max.)
Thermal Cycles (63 cycles)under 95-100°C 16kV
Impulse voltage test75/95kV no flashover
A.C. with stand test16kV, 15 min, no flashover
Humidity test (Indoor)No flashover, tracking erosion or mechanical damage  occured at 300hrs, 8kV
Salt Fog test (Outdoor)No flashover, tracking erosion or mechanical damage occured at 1000hrs, 8kV no flashover, tracking
Order Reference for Pre-moulded Terminations Indoor & Outdoor 1 Core
12 kV, 1 Core 
Indoor 
Terminations
Cable Cross 
Section (mm²)
Product Code
35 - 70AYDPMI-12 - 1 x 35-70
95 - 240AYDPMI-12 - 1 x 95-240
185- 300AYDPMI-12 - 1 x 185-300
300 - 400AYDPMI-12 - 1 x 300-400
500 - 630AYDPMI-12 - 1 x 500-630
12 kV, 1 Core 
Outdoor 
Terminations
Cable Cross 
Section (mm²)
Product Code
35 - 70AYDPMO-12 - 1 x 35-70
95 - 240AYDPMO-12 - 1 x 95-240
185- 300AYDPMO-12 - 1 x 185-300
300 - 400AYDPMO-12 - 1 x 300-400
500 - 630AYDPMO-12 - 1 x 500-630