Cold Shrinkable Straight Terminations are Tested as per HD629-1 & IEC-60502-4 / IS:13573
| Testing Items Uo/U/Um | 19/33/36 kV |
|---|---|
| A.C. withstand test | 86kV, 5min, no flashover |
| Partial discharge test | 33kV<10pc (Max.) |
| Thermal Cycles (63 cycles) | under 95-100°C 48kV |
| Impulse voltage test | 170/200kV no flashover |
| A.C. with stand test | 48kV, 15 min, no flashover |
| Humidity test (Indoor) | No flashover, tracking erosion or mechanical damage occured at 300hrs, 24kV |
| Salt Fog test (Outdoor) | No flashover, tracking erosion or mechanical damage occured at 1000hrs, 24kV no flashover, tracking |
| 36 kV, 3 Core Indoor Terminations | Cable Cross Section (mm²) | Product Code |
| 35 - 70 | AYDCSI-36 - 3 x 35-70 | |
| 95 - 240 | AYDCSI-36 - 3 x 95-240 | |
| 185 - 300 | AYDCSI-36 - 3 x 185-300 | |
| 300 - 400 | AYDCSI-36 - 3 x 300-400 | |
| 500 | AYDCSI-36 - 3 x 500 |
| 36 kV, 3 Core Outdoor Terminations | Cable Cross Section (mm²) | Product Code |
| 35 - 70 | AYDCSO-36 - 3 x 35-70 | |
| 95 - 240 | AYDCSO-36 - 3 x 95-240 | |
| 185 - 300 | AYDCSO-36 - 3 x 185-300 | |
| 300 - 400 | AYDCSO-36 - 3 x 300-400 | |
| 500 | AYDCSO-36 - 3 x 500 |