Cold Shrink Cable Terminations 3 Core for 24kV (XLPE/EPR Insulated Cable)

Cold Shrink Cable Terminations 3 Core for 24kV (XLPE/EPR Insulated Cable)

  1. Simple Structure, pre-fabricated, & factory tested.
  2. Ready to use and easy to install.
  3. Made from LSR, delivering better Electrical and Outdoor Performance.
  4. In compliance with HD629-1 & IEC-60502-4.
  5. Lugs are optional. Compression or shear head mechanical lugs supplied on request.
Specifications

Cold Shrinkable Straight Terminations are Tested as per HD629-1 & IEC-60502-4 / IS:13573

Testing Items Uo/U/Um12.7/22/24 kV
A.C. withstand test58kV, 5min, no flashover
Partial discharge test22kV<10pc (Max.)
Thermal Cycles (63 cycles)under 95-100°C 32kV
Impulse voltage test125/150kV no flashover
A.C. with stand test32kV, 15 min, no flashover
Humidity test (Indoor)No flashover, tracking erosion or mechanical damage  occured at 300hrs, 16kV
Salt Fog test (Outdoor)No flashover, tracking erosion or mechanical damage occured at 1000hrs, 16kV no  flashover, tracking
Order Reference for Cold Shrink Terminations Indoor & Outdoor 3 Core
24 kV, 3 Core 
Indoor 
Terminations
Cable Cross 
Section (mm²)
Product Code
35 - 70AYDCSI-24 - 3 x 35-70
95 - 240AYDCSI-24 - 3 x 95-240
185 - 300AYDCSI-24 - 3 x 185-300
300 - 400AYDCSI-24 - 3 x 300-400
500AYDCSI-24 - 3 x 500
24 kV, 3 Core 
Outdoor 
Terminations
Cable Cross 
Section (mm²)
Product Code
35 - 70AYDCSO-24 - 3 x 35-70
95 - 240AYDCSO-24 - 3 x 95-240
185 - 300AYDCSO-24 - 3 x 185-300
300 - 400AYDCSO-24 - 3 x 300-400
500AYDCSO-24 - 3 x 500