Cold Shrinkable Straight Terminations are Tested as per HD629-1 & IEC-60502-4 / IS:13573
| Testing Items Uo/U/Um | 12.7/22/24 kV |
|---|---|
| A.C. withstand test | 58kV, 5min, no flashover |
| Partial discharge test | 22kV<10pc (Max.) |
| Thermal Cycles (63 cycles) | under 95-100°C 32kV |
| Impulse voltage test | 125/150kV no flashover |
| A.C. with stand test | 32kV, 15 min, no flashover |
| Humidity test (Indoor) | No flashover, tracking erosion or mechanical damage occured at 300hrs, 16kV |
| Salt Fog test (Outdoor) | No flashover, tracking erosion or mechanical damage occured at 1000hrs, 16kV no flashover, tracking |
| 24 kV, 3 Core Indoor Terminations | Cable Cross Section (mm²) | Product Code |
| 35 - 70 | AYDCSI-24 - 3 x 35-70 | |
| 95 - 240 | AYDCSI-24 - 3 x 95-240 | |
| 185 - 300 | AYDCSI-24 - 3 x 185-300 | |
| 300 - 400 | AYDCSI-24 - 3 x 300-400 | |
| 500 | AYDCSI-24 - 3 x 500 |
| 24 kV, 3 Core Outdoor Terminations | Cable Cross Section (mm²) | Product Code |
| 35 - 70 | AYDCSO-24 - 3 x 35-70 | |
| 95 - 240 | AYDCSO-24 - 3 x 95-240 | |
| 185 - 300 | AYDCSO-24 - 3 x 185-300 | |
| 300 - 400 | AYDCSO-24 - 3 x 300-400 | |
| 500 | AYDCSO-24 - 3 x 500 |
Have a question, idea, or requirement? Drop us a message and our team will get back to you with clear answers no fluff, no delay.