Cold Shrink Cable Terminators 1 Core for 36kV (XLPE/EPR Insulated Cable)

Cold Shrink Cable Terminators 1 Core for 36kV (XLPE/EPR Insulated Cable)

  1. Simple Structure, pre-fabricated, & factory tested.
  2. Ready to use and easy to install.
  3. Made from LSR, delivering better Electrical and Outdoor Performance.
  4. In compliance with HD629-1 & IEC-60502-4.
  5. Lugs are optional. Compression or shear head mechanical lugs supplied on request.
Specifications

Cold Shrinkable Straight Terminations are Tested as per HD629-1 & IEC-60502-4 / IS:13573

Testing Items Uo/U/Um19/33/36 kV
A.C. withstand test86kV, 5min, no flashover
Partial discharge test33kV<10pc (Max.)
Thermal Cycles (63 cycles)under 95-100°C 48kV
Impulse voltage test170/200kV no flashover
A.C. with stand test48kV, 15 min, no flashover
Humidity test (Indoor)No flashover, tracking erosion or mechanical damage occured at 300hrs, 8kV
Salt Fog test (Outdoor)No flashover, tracking erosion or mechanical damage occured at 1000hrs, 8kV no flashover, tracking
Order Reference for Cold Shrink Straight Terminations 1 Core
36 kV, 1 Core 
Indoor 
Terminations
Cable Cross 
Section (mm²)
Product Code
35 - 70AYDCSI-36 - 1 x 35-70
95 - 240AYDCSI-36 - 1 x 95-240
185- 300AYDCSI-36 - 1 x 185-300
300 - 400AYDCSI-36 - 1 x 300-400
500 - 630AYDCSI-36 - 1 x 500-630
800 - 1000AYDCSI-36 - 1 x 800-1000
36 kV, 1 Core
Outdoor 
Terminations
Cable Cross 
Section (mm²)
Product Code
35 - 70AYDCSO-36 - 1 x 35-70
95 - 240AYDCSO-36 - 1 x 95-240
185- 300AYDCSO-36 - 1 x 185-300
300 - 400AYDCSO-36 - 1 x 300-400
500 - 630AYDCSO-36 - 1 x 500-630
800 - 1000AYDCSO-36 - 1 x 800-1000